ESP Motor and Cable Sizing - Horsepower, Amperage, and Voltage Drop
Overview
The motor and cable are the power delivery system for an ESP installation. The motor must provide sufficient horsepower to drive the pump at the required brake horsepower, and the cable must deliver adequate voltage and current from the surface to the motor without excessive losses.
Undersized motors lead to overloading, overheating, and premature failure. Undersized cables cause excessive voltage drop, reduced motor performance, and wasted energy. Both components must be sized together as part of an integrated electrical system design.
Motor Horsepower Requirements
Required Motor HP
The motor must deliver at least the brake horsepower demanded by the pump:
Where:
- = brake horsepower required by the pump
- = motor efficiency (typically 0.80 to 0.92)
- = power consumed by the seal/protector section (typically 2-10 HP)
In most practical designs, the protector losses are small relative to the pump BHP and are accounted for in the motor selection margin.
Brake Horsepower from Pump
The pump BHP depends on the number of stages, flow rate, and fluid properties:
Where is the power consumption per stage at the operating rate (from the manufacturer's curve), and is the fluid specific gravity.
Alternatively, from hydraulic horsepower and efficiency:
Motor Selection
Motors are available in discrete nameplate HP ratings. The selected motor must satisfy:
Standard ESP motor sizes (HP): 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200, 250, 300, 400, 500, 600, 750, 1000.
Motor Load Factor
Definition
The load factor is the ratio of actual shaft load to the motor's nameplate rating:
Load Factor Guidelines
| Load Factor | Status | Consequence |
|---|---|---|
| < 0.70 | Underloaded | Reduced motor efficiency, higher unit cost |
| 0.70 - 0.90 | Optimal | Good efficiency and reliability |
| 0.90 - 1.00 | Fully loaded | Maximum efficiency, minimal margin |
| 1.00 - 1.10 | Overloaded (service factor) | Acceptable short-term, reduced life |
| > 1.10 | Severely overloaded | Not recommended, rapid overheating |
Most ESP motors have a service factor of 1.0 to 1.15, meaning they can sustain 100-115% of nameplate HP under certain conditions. However, operating above nameplate reduces motor life due to increased winding temperature.
Temperature and Load
Motor winding temperature rise is approximately proportional to the square of the load:
A motor at 110% load generates approximately 21% more heat than at 100% load, significantly reducing insulation life.
Motor Amperage
Nameplate Current
ESP motors are rated at a specific voltage and amperage at full load. The relationship between power, voltage, and current for a three-phase motor:
Where:
- = motor terminal voltage (V)
- = motor current (A)
- = power factor (typically 0.80 to 0.85 for ESP motors)
- = motor efficiency (decimal)
- 746 = watts per horsepower
Rearranging for motor current at any load:
Current at Partial Load
At partial load, motor current does not decrease linearly with HP because magnetizing current remains roughly constant:
Where is typically 30-50% of for ESP motors.
Typical Motor Parameters
| Motor HP | Voltage (V) | Current (A) | Motor OD (in) |
|---|---|---|---|
| 30 | 460 | 40 | 3.75 |
| 75 | 750 | 62 | 4.56 |
| 100 | 1,000 | 62 | 4.56 |
| 200 | 1,500 | 83 | 5.43 |
| 400 | 2,400 | 103 | 5.43 |
| 750 | 3,300 | 141 | 7.38 |
Note: These are representative values. Actual parameters vary by manufacturer and motor series.
Motor Temperature Considerations
Heat Dissipation
The ESP motor is cooled by the well fluid flowing past the motor housing. The minimum fluid velocity past the motor for adequate cooling:
The annular velocity between the motor and casing:
Where all dimensions are in consistent units.
Temperature Rating
| Motor Class | Maximum Winding Temperature | Typical Application |
|---|---|---|
| Standard | 280 F (138 C) | Wells with BHT < 200 F |
| High-temp | 350 F (177 C) | Wells with BHT 200-300 F |
| Ultra high-temp | 400 F (204 C) | HPHT wells |
The motor winding temperature equals the ambient well temperature plus the temperature rise from internal losses:
Cable Voltage Drop
Importance
The cable delivers three-phase power from the surface to the downhole motor. Due to the cable's electrical resistance, voltage is lost along the cable length. If the voltage reaching the motor terminals is too low, the motor cannot develop rated torque and will overheat.
Voltage Drop Calculation
For a three-phase cable, the voltage drop per 1,000 ft of cable:
Where:
- = voltage drop per 1,000 ft (V/1000 ft)
- = motor current (A)
- = cable resistance per 1,000 ft per conductor (ohm/1000 ft)
The total voltage drop along the full cable length:
Where is the cable length in feet (typically equal to or slightly greater than the pump setting depth).
Temperature Effect on Resistance
Cable resistance increases with temperature. The resistance at downhole temperature:
Where:
- = resistance at 77 F (published catalog value, ohm/1000 ft)
- = temperature coefficient of resistance (0.00214 per F for copper)
- = average cable temperature (F)
The average cable temperature is typically estimated as:
Cable Resistance by Size
| AWG Size | Conductor Area (kcmil) | (ohm/1000 ft) | Max Ampacity (A) |
|---|---|---|---|
| 1 | 83.7 | 0.139 | 115 |
| 2 | 66.4 | 0.175 | 95 |
| 4 | 41.7 | 0.278 | 70 |
| 6 | 26.3 | 0.442 | 55 |
Note: Resistance values are per conductor. Ampacity ratings are approximate and depend on cable construction, insulation type, and installation conditions.
Cable Size Selection
Selection Criteria
Cable size must satisfy two independent requirements:
- Ampacity: The cable must carry the motor current without exceeding its thermal rating
- Voltage drop: The voltage drop must be within acceptable limits
Ampacity Requirement
I_{cable\text{-}rating} \geq I_{motor} \times 1.10 \quad \text{(10% margin)}Voltage Drop Requirement
The voltage drop should not exceed a percentage of the motor nameplate voltage:
Common criteria:
| Criterion | Maximum Voltage Drop |
|---|---|
| Conservative | 3% of motor nameplate voltage |
| Standard | 5% of motor nameplate voltage |
| Aggressive | 8% of motor nameplate voltage |
| Rule of thumb | 30 V per 1,000 ft of cable |
Minimum Cable Size
The minimum cable size is the larger (lower AWG number) of:
- The size that satisfies the ampacity requirement
- The size that satisfies the voltage drop requirement
Where lower AWG numbers indicate larger cables.
Selection Workflow
Power Loss in Cable
Cable Power Loss
The electrical power dissipated as heat in the cable:
Where:
- = power loss in cable (watts)
- = motor current per phase (A)
- = resistance at temperature per conductor per 1,000 ft (ohm/1000 ft)
- = cable length (ft)
- Factor of 3 accounts for three conductors
Converting to horsepower:
Cable Loss as Percentage of Total Power
Typical Cable Losses
| Cable AWG | Motor Amps | Cable Length (ft) | Power Loss (HP) | Loss % |
|---|---|---|---|---|
| 2 | 60 | 6,000 | 8.0 | 3.2% |
| 2 | 60 | 10,000 | 13.3 | 5.3% |
| 1 | 80 | 8,000 | 14.2 | 3.8% |
| 4 | 40 | 5,000 | 4.5 | 3.6% |
| 4 | 40 | 12,000 | 10.7 | 8.6% |
Note: Values calculated at 77 F. At higher temperatures, losses increase due to higher resistance.
Surface Electrical System
Required Surface Voltage
The surface transformer or VSD must supply sufficient voltage to overcome the cable drop and deliver rated voltage to the motor:
VSD Considerations
When a Variable Speed Drive (VSD) is used:
- Voltage scales with frequency:
- At reduced speed, motor voltage and current change
- Cable voltage drop changes with current
The VSD output voltage at any frequency:
Where is the operating frequency and is the base frequency (typically 60 Hz).
System Efficiency
The overall electrical efficiency from surface to pump shaft:
Where:
| Component | Typical Efficiency |
|---|---|
| VSD | 95 - 97% |
| Cable | 92 - 98% (depends on length and size) |
| Motor | 80 - 92% |
| Overall electrical | 70 - 87% |
Design Example
Given Data
| Parameter | Value |
|---|---|
| Pump BHP | 150 HP |
| Motor selected | 200 HP, 1,500 V, 83 A |
| Cable length | 8,000 ft |
| Surface temperature | 80 F |
| Bottomhole temperature | 220 F |
| Cable type | #2 AWG copper, round |
Calculations
Load Factor:
Average Cable Temperature:
Cable Resistance at Temperature:
Voltage Drop:
Voltage Drop Percentage:
This exceeds the 5% criterion. The designer should either:
- Increase cable size to #1 AWG (reduces resistance)
- Select a higher-voltage motor (reduces current for same HP)
With #1 AWG Cable:
Still high. A higher voltage motor (e.g., 2,400 V, 52 A) would yield:
This meets the 5% criterion with #1 AWG cable.
Cable Power Loss (final design, 2,400 V motor, #1 AWG):
Related Topics
- ESP System Design Overview -- Complete design workflow with motor and cable steps
- ESP Pump Performance -- Determining BHP requirements for motor sizing
- ESP Gas Handling -- Gas effects on pump load and motor sizing
- ESP Viscosity Corrections -- Viscous BHP for motor sizing
- Well Flow Overview -- Production rate targets driving ESP sizing
References
Takacs, G. (2009). Electrical Submersible Pumps Manual: Design, Operations, and Maintenance. Gulf Professional Publishing.
Baker Hughes. (2021). ESP Cable Engineering Handbook. Baker Hughes Technical Publications.
IEEE Standard 1580. (2010). Recommended Practice for Marine Cable for Use on Shipboard and Fixed or Floating Platforms. IEEE.
Brown, K.E. (1984). The Technology of Artificial Lift Methods, Vol. 2b. PennWell Books.
Neely, A.B. and Patterson, M.M. (1984). "Soft Starting the Submersible Pump." SPE-12484-MS, Formation Damage Control Symposium, Bakersfield, California.